AIL12 - Monitoring Of Presence / Drop-out Of 3 Phase Voltages In The Low Voltage Network

etthv

  • CLIENT: IFT InForm Technologies

 

The product consists of two parts. AIL12-MASTER in connection with AIL12-EI is a device designed to monitor the presence / drop-out of three phase voltages in the low voltage network. AIL12-MASTER is a concentrator designed to monitor, collect and record data from the AIL12-SLAVE measurement units through the RS-485 interface.

AIL12-SLAVE

Basic properties of output interface:

  • Communication with AIL12-MASTER through RS-485 according to proprietary protocol

  • Communication speed of RS-485 9600 Bd

  • Phoenix QC 1/4-ST-BUS type connector

  • Possibility to configure the address by a mechanical switch in the 1 to 16 range

Basic properties of input interface:

  • Monitoring of presence or drop-out of three mains voltages

  • Voltage presence LED signalization for every input - S1 to S3

  • Measurement inputs in connection with AIL12-EI conform with STN EN 61010-1: max. 600 V, CATIII

  • 1 s measurement interval

  • Detection of input voltage presence > 70 V rms

  • Connection of inputs through external AIL12-EI impedance to screw clamps with maximal section of connected wires 2,5 mm2

Technical parameters

POWER SUPPLY VOLTAGE +12 V to +24 V DC
POWER SUPPLY CURRENT max. 10 mA
BUILT-IN POWER SUPPLY CURRENT PROTECTION 100 mA return fuse
COMMUNICATION OUTPUT INTERFACE

RS-485 –  proprietary protocol

COMMUNICATION SPEED THROUGH RS-485 9600 Bd
INPUTS

3, connected through external AIL12-EI impedance

MAXIMAL INPUT MEASURED VOLTAGE

max. 600V, CATIII, according to STN EN 61010-1

MEASUREMENT INTERVAL

1 s

DETECTION OF PRESENCE OF INPUT VOLTAGE

> 70 V rms

OPERATING TEMPERATURE RANGE

-25 °C to 70 °C

ENVIRONMENT CONTAMINATION

II category of contamination

MECHANICAL DESIGN

plastic box, dimensions 110 mm x 57 mm

DEVICE COVER

IP20

 

 

AIL12-MASTER

Basic properties of input interface:

  • Monitoring of presence and collection of data from 16 AIL12-S measurement units

  • Communication with AIL12-S through RS-485 according to proprietary protocol

  • Communication speed of RS-485 9600 Bd

  • Output connector: screw clamps with maximal section of connected wires 2,5 mm2

Possibility to configure:

  • Period of requesting of Skalar to communicate in the range 10 - 2400 min

  • Period begins always after the last communication

  • Time filter of voltage build-up in the range of 1 to 240 s

  • Time filter of voltage drop-out in the range of 1 to 240 s

  • Time, device internal clock

Basic properties of output interfaces:

  • Output to communication / superior system through RS-485, protocol according to the STN EN 62056-21, mode C norm, with special and also universal serial number. Universal serial number has 12089999 form

  • Communication speed of RS-485 9600 Bd

  • Event signalization (drop-out or recovery of voltage) by non-potential switch contact (max. 100 V, 100 mA), turned off in the default position

  • Connection of switching contact as well as communication line to screw clamps with maximal section of connected wires 2,5 mm2

Technical parameters

POWER SUPPLY VOLTAGE +12 V to +24 V DC
POWER SUPPLY CURRENT max. 30 mA
BUILT-IN POWER SUPPLY CURRENT PROTECTION 600 mA return fuse
RECORDS MEMORY

last 500 events

REAL-TIME CLOCK 10 year backup
COMMUNICATION OUTPUT MASTER INTERFACE

RS-485 –  own protocol

COMMUNICATION SPEED THROUGH MASTER RS-485

9600 Bd

INTERVAL OF PERIODICAL READOUT OF 16 AIL12-S

1 s

COMMUNICATION OUTPUT INTERFACE SLAVE

RS-485 –  according to STN EN 62056-21 norm, mode C

GALVANIC SEPARATION OF RS-485 SLAVE

≤ 450 V rms  I to III

COMMUNICATION SPEED THROUGH RS-485 SLAVE

9600 Bd

SIGNALIZATION OUTPUT INTERFACE

non-potential switching contact max. 100 V, 0,1

GALVANIC SEPARATION OF SWITCHING CONTACT

500 V according to ICE255-5

OPERATING TEMPERATURE RANGE

-25 °C to 70 °C

MECHANICAL DESIGN

DIN bar box, 2MD – 35 mm size

 

© ANDIS 2024. Design and programming by Soyamedia